New Process for Coal-Containing Wastewater Treatment in Thermal Power Plants

2026-11-20 10:45:52
立即下载


Thermal power plants are an important part of power generation and depend on coal as a key energy source. Coal is mainly burned to generate electricity, and the choice of coal directly affects generation efficiency and environmental performance. Common coals include anthracite, bituminous coal and lignite. Anthracite has a high calorific value, low ash and very low levels of sulphur, phosphorus and other harmful substances, making it one of the preferred coals for power plants, but it is expensive and in limited supply. Bituminous coal also has a high calorific value but a relatively high sulphur content and tends to pollute the air when burned, so it must be desulphurised and dedusted before use. Lignite has a lower calorific value but is abundant and relatively cheap, and is widely used in less developed regions or where fuel prices are high.


Sources and characteristics of coal-containing wastewater in thermal power plants

Coal-containing wastewater is unavoidable in thermal power plant operations. It comes mainly from coal transport, storage, crushing, screening and washing. Specifically:

1. Coal washing: in wet washing, water consumption of 2–8 m³ per tonne of coal generates wastewater.

2. Coal transport: friction and impact during transport generate coal dust and fines, which enter the wastewater system with the water.

3. Equipment cleaning: cleaning the coal handling equipment — crushers, screens and the like — also produces coal-containing wastewater.

Coal-containing wastewater usually carries large amounts of dust particles, suspended solids and some organic matter, and is black or greyish black; the bulk density of the suspended solids is generally 2.3 g/cm3. Discharging it untreated pollutes the environment and wastes valuable water resources.


General treatment process for coal-containing wastewater in thermal power plants

The treatment process usually includes the following steps:

1. Wastewater collection: coal-containing wastewater is collected in a coal settling pond for primary settling to remove coarse coal fines and suspended solids.

2. Coagulation and sedimentation: coagulant aids (such as polyaluminium chloride, PAC, and polyacrylamide, PAM) are dosed so that fine particles aggregate into larger flocs that settle out easily.

3. Filtration: the settled wastewater passes to filtration units to remove further suspended solids and fine particles. Common equipment includes hydrocyclones and multi-media filters.

4. Sludge discharge: sludge from settling and filtration is thickened and dewatered, then discharged or put to resource use.

Common processes for coal-containing wastewater in thermal power plants include chemical coagulation plus membrane treatment, high-efficiency microporous ceramic filtration, coagulation plus inclined-plate settling plus filtration, and electrocoagulation plus centrifugal settling plus filtration. Each has its own advantages and drawbacks and must be selected and optimised for the plant's actual conditions.


In view of the characteristics of coal wastewater from thermal power plants, SINOKLE Co., Ltd. has drawn on its independently developed technology CDFU and proposed a new process that treats coal wastewater efficiently and meets process requirements.

sinokle

New process for coal wastewater treatment in thermal power plants


sinokle 

CDFU Diagram of the cyclonic dissolved gas flotation unit in operation

 

 CDFU - Cyclonic Dissolved Gas Flotation Unit: a compact cyclonic dissolved gas flotation unit that effectively integrates centrifugal separation, dissolved gas flotation and ultrafine bubble generation in a single hybrid device for efficient separation of oily and suspended-solids-laden wastewater.

sinokle 


Process features

Mature process with strong shock resistance and stable, reliable performance; no chemicals, no aged oil and no secondary pollution, with good environmental benefits; short flow, small footprint, few moving parts, simple operation and low cost; a two-stage configuration with strong shock resistance that ensures stable, reliable downstream treatment and high economic returns; advanced filtration technology with stable performance and high precision that keeps effluent reliably within standard.




Mobile phone/Whatsapp